Beck-930 Series Differential pressure switch

Beck-930 Adjustable differential pressure switch for monitoring overpressure, vacuum and differential pressure of air or other non-combustible, non-aggressive gases.

The switching pressure can be adjusted without a pressure gauge using a scaled adjustment knob. Various versions with overlapping adjustment ranges between 0.2 mbar and 50 mbar are available for this purpose. As standard, the pressure switch is equipped with a transparent cover of protection class IP54.

We have three variants such as:

  • Differential pressure switch 930 adjustable
  • Differential pressure switch 930 EX adjustable
  • Differential pressure switch 930 with UL approval adjustable

*All variants is adjustable from 20 to 5000 pascal.

Applications

Beck-930 Adjustable differential pressure switch for monitoring overpressure, vacuum and differential pressure of air or other non-combustible, non-aggressive gases.

Possible fields of application include:

  • Monitoring air filters and ventilators
  • Monitoring industrial cooling-air circuits
  • Overheating protection for fan heaters
  • Monitoring flows in ventilation ducts
  • Controlling air and fire-protection flaps
  • Frost protection for heat exchangers

Version

With this pressure switch, the switching pressure can be adjusted without a pressure gauge using a scaled adjustment knob.

TypeAdjustment range Switchig diferentialRepeatability of the switching pressure
930.8020  –  200 Pa10 Pa±5 %,    min. ±5 Pa
930.80B20 –  300 Pa10 Pa±5 %,    min. ±5 Pa
930.8430 –  400 Pa15 Pa±5 %,    min. ±5 Pa
930.8350 –  500 Pa20 Pa±2.5 %, min. ±5 Pa
930.85200 –  1000 Pa100 Pa±1 %,    min. ±5 Pa
930.85B100 –  1000 Pa100 Pa±1 %,    min. ±5 Pa
930.86500 –  2500 Pa150 Pa±1 %,    min. ±5 Pa
930.871000 –  4000 Pa250 Pa±1 %,    min. ±5 Pa
930.87B1000 –  5000 Pa250 Pa±1 %,    min. ±5 Pa
  • typically, at beginning of setting range.

Switching pressure specifications apply to vertical installation which is also the recommended position with pressure-pipe connections pointing downwards. If the switches are installed horizontally with AMP connection terminals uppermost, the switching values are approx. 20 Pa higher.

Specification

Maximum operating pressure

  • 10 kPa for all pressure ranges.

Medium

  • Air, non-combustible and non-aggressive gases.

Temperature range

  • Medium and ambient temperature from –20°C to +85°C. Storage temperature from –40°C to +85°C.

Diaphragm material

  • Silicone, tempered at 200°C, free of gas emissions. Other materials available on request.

Pressure connections

  • 2 plastic pipe connection pieces (P1 and P2), external diameter 6.0 mm: P1 for connection to higher pressure (marked +) P2 for connection to lower pressure (marked –)

Housing materials

  • Switch body and a cover of plastic.

Weight

  • With cover 150 g, without cover 110 g.

Mechanical working life

  • Over 106 switching operations.

Electrical rating

  • Standard version:   max. 1.5 A (0.4 A) / 250 VAC
  • Low-voltage version: max. 0.1 A / 24 VDC

Electrical connections

  • AMP flat plug 6.3×0.8 mm in accordance with DIN 46244 or push-on screw terminals. Cable conduit with cable strain relief.

Arrangement of contacts

  • 1 Break contact 2 Operating contacts 3 Power supply line

 Protection category

  • IP 54 with cover, IP 00 without cover.

CE Conformity

  • each depending on technical specification: Low Voltage Directive 2006/95/EC; RoHS Directive 2011/65/EC; Gas Appliance Directive 2009/142/EC; ATEX- Directive 2014/34/EC; ANSI UL508; CSA.

Specifications according to EN1854

  • Class of control and regulation function: A Deviation: ≤±15 %, min. ±10 Pa Drift: ≤±15 %

Baca Juga :

author

Rudy Wiratama

rudywinoto.com/wmablog.com/flowmasonic.com

Similar Posts

Discover more from Indonesia Industrial Parts

Subscribe now to keep reading and get access to the full archive.

Continue reading